Z203509-0C PAGE 1 ©2011 Veris Industries USA 800.354.8556 or +1.503.598.4564 / suppor[email protected] 07111
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
TM
POWER MONITORING
INSTALLATION GUIDE
H89 20-4
Installer’s Specifications
LonWorks® Network Free topology transceiver, 78 kbps
Modbus Network RTU 9600 BAUD, 8N1 format
Network Variable Type Fixed point real
Input Power 16-24 VAC/DC, 100mA (max.)
Temperature Range 0 to 60°C (32 to 140°F)
Humidity Range 0 - 95% non-condensing
DIMENSIONS
LONTalk Integration Node For Use With
H704 and H663 Branch Current Monitors (BCM)
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
This equipment must only be installed and serviced by qualified electrical personnel.
Read, understand and follow the instructions before installing this product.
Turn off all power supplying equipment before working on or inside the equipment.
Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
DANGER
NOTICE
This product is not intended for life or safety applications.
Do not install this product in hazardous or classified locations.
The installer is responsible for conformance to all applicable codes.
Mount this product inside a suitable fire and electrical enclosure.
FCC PART 15 INFORMATION
NOTE: This equipment has been tested by the manufacturer and found
to comply with the limits for a class A digital device, pursuant to part
15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference when the equipment is
operated in a commercial environment. This equipment generates,
uses, and can radiate radio frequency energy and, if not installed and
used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in
a residential area is likely to cause harmful interference in which case
the user will be required to correct the interference at his own expense.
Modifications to this product without the express authorization of
Veris Industries nullify this statement.
PRODUCT IDENTIFICATION
H89 20-4
4.25"
(108 mm)
2.12
(54 mm)
1.16"
(30 mm)
4.25"
(108 mm)
1.53"
(39 mm)
C
L
C
L
C
L
Wire Opening
Wire Opening
Wire Opening
1.16"
(30 mm)
SERVICE TX RX
MODBUS
OP
Hawkeye
®
8920 Series
MODEL DESCRIPTION
H8920-4 H704/H663 to LonTalk® integration node
Vue de la page 0
1 2 3 4 5

Résumé du contenu

Page 1 - H89 20-4

Z203509-0C PAGE 1 ©2011 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 07111Alta Labs, Enercept, Enspector, Hawkeye,

Page 2 - INSTALLATION GUIDE

Z203509-0C PAGE 2 ©2011 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 07111Alta Labs, Enercept, Enspector, Hawkeye,

Page 3

Z203509-0C PAGE 3 ©2011 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 07111Alta Labs, Enercept, Enspector, Hawkeye,

Page 4

Z203509-0C PAGE 4 ©2011 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 07111Alta Labs, Enercept, Enspector, Hawkeye,

Page 5 - BRANCH CURRENT MONITORS

Z203509-0C PAGE 5 ©2011 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 07111Alta Labs, Enercept, Enspector, Hawkeye,

Commentaires sur ces manuels

Pas de commentaire