Veris-industries TJ SERIES Datasheet Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Équipement Veris-industries TJ SERIES Datasheet. Veris Industries TJ SERIES Datasheet User Manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 2
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
TEMPERATURE
VERIS INDUSTRIES
800.354.8556
+1 503.598.4564
www.veris.com
SPECIFICATIONS
Wiring 22 AWG; 2-wire: RTD/Thermistor
Probe Stainless Steel
Linitemp:
Input Power 5 to 30VDC
Output 1µA/°C or 10mV/°C
Operating Temperature Probe: -25° to 105°C (-13° to 221°F); Wiring: up to 75°C (167°F)
Resistive:
RTD/Thermistor See table, facing page
Accuracy:
Calibration Error 1.5°C (2.7°F) typical; 2.5°C (4.5°F) max. at 25°C (7F)*
Error over Temperature 1.8°C (3.24°F) typical; 3.0°C (5.4°F) max. over 0° to 70°C (32° to 158°F) range;
2.0°C (3.6°F) typical, 3.5°C (6.3°F) max. over -25° to 105°C (-13° to 221°F) range
Increased cable length aects the readings of lower resistance RTDs (100R platinum, RTD).
* Room temperature error documented on each unit.
VAV Discharge Air Sensor For
Reheat Applications
VAV Discharge
Temperature Sensors
DESCRIPTION
The TJ Series temperature sensors are highly accurate and cost eective, with
trouble-free installation. The sensor is encased in a sturdy corrosion-resistant
stainless steel probe. A variety of RTD/thermistor sensor and probe length options
are available for maximum versatility in applications.
APPLICATIONS
VAV reheat boxes
Dual duct boxes
Fan coils
Prove that the hot water valve or electric heat is functioning properly
Check individual reheating stages
Check for hot water valve leaks
Determine if damper actuators are functioning on dual duct boxes
FEATURES
Stainless steel duct probe with mounting ange...quick, easy installation
5’ (1.5 m) plenum rated cable standard...eliminates need to splice
4” or 8” (102 mm or 204 mm) duct probes for application exibility
2-wire installation (optional quick disconnect)...installs in just a few
short minutes
Installation ready for VAV systems and plenum areas...saves money on job
commissioning and warranty service
TJ
TJ SERIES
HQ0001880.B 01131
Vue de la page 0
1 2

Résumé du contenu

Page 1 - Temperature Sensors

TEMPERATURE VERIS INDUSTRIES800.354.8556+1 503.598.4564www.veris.comSPECIFICATIONS Wiring 22 AWG; 2-wire: RTD/ThermistorProbe Stainless SteelLi

Page 2 - TEMPERATURE

TEMPERATURE800.354.8556+1 503.598.4564www.veris.comSensor TypeOptionProbe Length “L”B = 100R platinum, RTDC = 1k platinum, RTDD = 10k T2, Thermisto

Commentaires sur ces manuels

Pas de commentaire