Installation Guide
Current Monitoring
Z201169-0B Page 1 of 3 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / suppor[email protected] 09133
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
TM
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Follow safe electrical work practices.
See NFPA 70E in the USA, or applicable local codes.
This equipment must only be installed and serviced by qualified electrical personnel.
Read, understand and follow the instructions before installing this product.
Turn off all power supplying equipment before working on or inside the equipment.
Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
A qualied person is one who has skills and knowledge related to the construction and
operation of this electrical equipment and the installation, and has received safety
training to recognize and avoid the hazards involved. NEC2011 Article 100
No responsibility is assumed by Veris Industries for any consequences arising out of the
use of this material.
DANGER
NOTICE
This product is not intended for life or safety applications.
Do not install this product in hazardous or classified locations.
The installer is responsible for conformance to all applicable codes.
Mount this product inside a suitable fire and electrical enclosure.
Product Overview
The H932 is a current-sensitive device that monitors current (amperage) in any of three eld-selectable ranges;
0-30, 0-60, or 0-120 amperes. These ranges represent the maximum current that can be applied to the monitored
conductor. The H932 transforms the monitored current into a 0-5 VDC output suitable for connection to building
controllers or other appropriate data acquisition equipment. It is also equipped with a command relay.
The H932 housing oers unprecedented mounting exibility. The mounting bracket can be attached in three
dierent places. Additionally, the bracket is compatible with the Veris AH01 DIN Rail clip, allowing DIN mounting.
H932
Split-Core Current Transducer with Relay,
0-5 VDC Output
TM
Specifications
Sensor Power
Induced from monitored conductor
Amperage Range
0 to 30/60/120 A (selectable)
Insulation Class
600VAC RMS
Relay
SPST, N.O., 24 VAC/DC
Frequency Range
50/60 Hz
Temperature Range
-15° to 60°C (5° to 140°F)
Humidity Range
10 - 90% RH, non-condensing
Accuracy
±2% full scale from 10% to 100% (selected range)
Response Time
2 sec.
Terminal Block Wire Size
24-14 AWG (0.2 to 2.1 mm
2
)
Terminal Block Torque
3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)
Agency Approvals
UL 508 open device listing
Dimensions
Removable Mounting Bracket
1.0”
(25 mm)
0.8”
(21 mm)
1.1”
(26 mm)
3.1”
(79 mm)
Self-gripping Iris
2.8”
(70 mm)
Ø 0.3”
(8 mm)
1.4”
(36 mm)
2.5”
(64 mm)
3.0”
(76 mm)
Bracket can
be mounted
on three sides
for added
installation
exibility.
Use DIN Rail Mounting clip
(Veris part number AH01) to
mount on standard DIN rail.
Vue de la page 0
1 2 3

Résumé du contenu

Page 1 - (Veris part number AH01) to

Installation GuideCurrent MonitoringZ201169-0B Page 1 of 3 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 09133 A

Page 2 - Installation

Z201169-0B Page 2 of 3 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 09133 Alta Labs, Enercept, Enspector, Hawke

Page 3 - Current Monitoring

Z201169-0B Page 3 of 3 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 09133 Alta Labs, Enercept, Enspector, Hawke

Commentaires sur ces manuels

Pas de commentaire