Veris-industries TW SERIES Install Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Équipement Veris-industries TW SERIES Install. Veris Industries TW SERIES Install User Manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 3
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
Installation Guide
Air Quality
Z206632-0A Page 1 of 3 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / suppor[email protected] 06132
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
TM
NOTICE
This product is not intended for life or safety applications.
Do not install this product in hazardous or classied locations.
Read and understand the instructions before installing
this product.
Turn off all power supplying equipment before working on it.
The installer is responsible for conformance to all applicable codes.
No responsibility is assumed by Veris Industries for any consequences arising out of the
use of this material.
Product Identification
Product Overview
The TW Series temperature sensors are equipped with highly accuracy RTD/thermistor devices and an analog
output compatible with most building control systems. To maintain accurate functionality, keep all vents free of
dust, debris, etc. These units are warranted for a period of ve years.
TW Series
Wall Mount Temperature Sensor
Specifications
Input Power
4-20mA mode: loop powered 12-30VDC only, 30mA max.
05-/0-10V mode: 12-30VDC/24VAC, 15mA max.
Temp Output
2-wire, loop powered 4-20mA or 3-wire, 0-5V/0-10VDC (switch selectable)
Ranges
10° to 35°C (50° to 95°F), 0° to 50°C (32° to 122°F) (jumper selectable)
Sensor Type
TW
Local Display
L = LCD
X = No
Setpoint/Override
Cal Certificate
0 = None
1 = Override*
2 = 1k Setpoint
3 = 10k Setpoint
4 = 1k Setpoint with override
5 = 10k Setpoint with override
0 = None
1 = 1 point Cal
2 = 2 point Cal
B = 100R platinum, RTD
C = 1k platinum, RTD
D = 10k T2, Thermistor
E = 2.2k, Thermistor
F = 3k, Thermistor
G = 10k CPC, Thermistor
H = 10k T3, Thermistor
J = 10k Dale, Thermistor
K = 10k w/11k shunt,Thermistor
M = 20k NTC, Thermistor
N = 1800 ohm, Thermistor
P = 10mV/°C, Linitemp
R = 10k US, Thermistor
S = 10k 3A221, Thermistor
T = 100k, Thermistor
U = 20k D Thermistor
W = 10k T2 high accuracy Thermistor
Y = 10kT3 high accuracy Thermistor
Z = 10k E1 Thermistor
Housing Color
None = Cloud White
B = Black
* Pushbutton override short circuits the RTD/thermistor output.
Vue de la page 0
1 2 3

Résumé du contenu

Page 1 - TW Series

Installation GuideAir QualityZ206632-0A Page 1 of 3 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 06132 Alta Lab

Page 2 - Installation

Z206632-0A Page 2 of 3 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 06132 Alta Labs, Enercept, Enspector, Hawke

Page 3

Z206632-0A Page 3 of 3 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 06132 Alta Labs, Enercept, Enspector, Hawke

Commentaires sur ces manuels