current monitoring
VERIS INDUSTRIES
800.354.8556
+1 503.598.4564
www.veris.com
Maximize Reliability
Minimize Installed Cost
FEATURES
● The H809 has a low (0.75 A) minimum setpoint...eliminates the need for
multiple wraps of the conductor through the sensor even on loads as
small as 1/5 HP
● H609 and H809 are small in size to t easily inside small starter enclosures
● Removable mounting bracket optimizes eld versatility
● Bracket on H909 can be installed in three dierent congurations...
added exibility
● Status LEDs for easy setup and local indication
● Adjustable trip point...precise current trip point setting
● Detect belt loss and mechanical failure...ideal for fan/pump status monitoring
● Easier to install than dierential pressure switches...eliminates long wiring runs
● 100% solid state...no moving parts to fail
● 5-year warranty
DESCRIPTION
Hawkeye x09 Series are high performance current switches, ideal for line voltage
loads. The devices are powered by the current being monitored.
APPLICATIONS
● Detecting belt loss, coupling shear, mechanical failure, and interlocking loads
● Verifying lighting circuit and other electrical service run times
● Monitoring status of industrial process equipment
● Monitoring status of critical motors (compressor, fuel, etc.)
SPECIFICATIONS
Sensor Power Induced from monitored conductor
Insulation Class 600VAC RMS
Frequency Range 50/60 Hz
Temperature Range -15° to 60°C (5° to 140°F)
Humidity Range 10-90% RH non-condensing
Hysteresis 10% (typical)
Terminal Block Wire Size 24-14 AWG (0.2 to 2.1 mm
2
)
Terminal Block Torque 3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)
Agency Approvals UL 508 open device listing; CE: EN61010-1:2001-02, CAT III, pollution degree 2, basic insulation
Do not use the LED status indicators as evidence of applied voltage
Current Switches:
Adjustable Trip Point,
High Voltage Output
Detect Belt Loss, Coupling
Shear, And Mechanical Failure
Year
Warranty
5
H709
H909
H609H809
Hx09 SERIES
TM
DETECTS BELT LOSS/COUPLING SHEAR!
DETECTS BELT LOSS/COUPLING SHEAR!
Now you can easily detect when drive belts slip, break, or pump couplings shear.
In fact, a typical HVAC motor that loses its load has a reduction of current draw
of up to 50%. That’s why our sensors are the industry standard for status.
Calibrated
Trip Point
O O
Fan/pump
On
Loss of Belt/Coupling Shear
Electrical
Failure
HQ0001755.B 01131