POWER Metering CTS
VERIS INDUSTRIES
800.354.8556
+1 503.598.4564
www.veris.com
Split-Core and Solid-Core
Designs for Flexibility
SPECIFICATIONS (Solid-Core)
Inputs:
Frequency Range 50-400 Hz
Leads 2 ft (0.6 m)
Accuracy:
Accuracy Varies at 60 Hz (see Ordering Information)
Outputs:
Output at Rated Current 5A
Mechanical:
Insulation 600VAC
Environmental:
Operating Temperature Range -30° to 55°C (-22° to 131°F)
Storage Temperature Range -30° to 105°C (-22° to 221°F)
Agency Approvals UL61010
SPECIFICATIONS (Split-Core)
Inputs:
Frequency Range 50/60 Hz
Leads 6 ft (1.8 m)
Accuracy:
Accuracy ±1% of reading from 10% to 100% of rated current
Outputs:
Output at Rated Current 5A
Mechanical:
Insulation 600VAC
Environmental:
Operating Temperature Range 2400A models only: -15° to 50°C (5° to 122°F); All other models: -15° to 60°C (5° to 140°F)
Storage Temperature Range -40° to 70°C (-40° to 158°F)
Humidity Range 0-95% noncondensing
Agency Approvals UL61010, EN61010
DESCRIPTION
Veris’ split-core and solid-core current transformers provide a 0-5AAC output for
use with transducers, data loggers, and chart recorders.
APPLICATIONS
● Data logging
● Recording
● Power monitoring
● Energy management
● Alternative energy monitoring
● Cost allocation
Current Transfomers,
5A Output
H681x-5A
AL BL CL
AL, BL, CL, & Hx-ASERIES
FEATURES
● Unique hinge design on split-cores...easy installation
● 5 Amp standard output...compatible with existing systems
● UL recognized
Year
Warranty
1
HQ0001817.B 01131