Z202027-0R PAGE 1 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / suppor[email protected] 01131
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
TM
ENVIRONMENTAL SENSORS
INSTALLATION GUIDE
Temperature Range Conguration
AA10
NOTICE
This product is not intended for life or safety applications.
Do not install this product in hazardous or classied locations.
Read and understand the instructions before installing
this product.
Turn off all power supplying equipment before working on it.
The installer is responsible for conformance to all applicable codes.
No responsibility is assumed by Veris Industries for any consequences arising out of the
use of this material.
DIMENSIONS
AA10
PRODUCT IDENTIFICATION
°C °F Order Code
-50 to 50 -58 to 122 1
0 to 50 32 to 122 2
0 to 100 32 to 212 3
10 to 35 50 to 95 4
0 to 150 32 to 302 5
-18 to 38 0 to 100 6
-18 to 121 0 to 250 7
-18 to 66 0 to 150 8
-29 to 66 -20 to 150 9
-60 to 70 -76 to 158 10
0 to 66 32 to 150 11
Example:
AA10C3
1.3”
(32mm)
nominal
1.5” (39mm)
1.0” (26mm)
INSTALLATION
1. Disconnect power to the control panel.
2. Wire the AA10 as shown in the Wiring section. For a 1-5 VDC output, use a 250 Ω
resistor (not included).
3. Refer to the Product Identication chart to determine the output temperature
range scaling.
SPECIFICATIONS
Transmitter:
Input Voltage 12 to 24VDC
Loop Resistance 250 Ω, 13.5V min.; 500 Ω, 18.5V min.
Output 4-20mA, 2-wire, loop powered; 1-5VDC with 250 Ω resistor
Transmitter Accuracy ±2.5% of span (typical)
Adjustment ±5% zero and span
Ambient Temperature 0° to 50°C (32° to 122°F)
Encapsulation Epoxy encapsulated
Sensor (sold separately):
Sensor Type RTD, Platinum, 100 Ω, 0.0385α
Sensor Accuracy ±0.30°C
Conversion Resistor 250Ω min. ¼ watt
WIRING
Current Output
POWER SUPPLY
12 to 24 VDC
DIGITAL CONTROL
RTD
Temperature
4-20 mA return
+
+
Voltage Output
POWER SUPPLY
12 to 24 VDC
DIGITAL CONTROL
RTD
Temperature
1-5VDC return
+
250Ω
+
AA10SPC01363
AA10SPC01365
AA10SPC01366
°C °F
-7 to 49 20 to 120
0 to 30 32 to 86
-10 to 10 14 to 50
PRODUCT OVERVIEW
The AA10 is intended for use with a 100 Ω platinum RTD (0.0385α) to provide either a
4-20 mA or a 1-5 VDC temperature signal.