current monitoring
VERIS INDUSTRIES
800.354.8556
+1 503.598.4564
www.veris.com
DESCRIPTION
The Hawkeye 931 and 951 provide accurate load trending information with a
proportional 4-20mA output signal. These devices oer three amperage ranges for
versatility, with easy slide-switch selection. The command relay is fully integrated in
the device, but it is isolated from the current sensor. This combination makes these
products ideal for start/stop control and status monitoring of motors, using one
device instead of two.
APPLICATIONS
Load trending
Motor control
Positive proof of ow
FEATURES
Loop-powered analog current sensor with integral start/stop command relay
Reduces the number of installed components...saves time and space
Self-gripping split-core for fast retrot installation...no need to remove
conductor
One device to install for start/stop & status...reduces installation charges
Power the current sensor and receive the 4-20mA signal with only two wires...
fewer wires required than with traditional 3-wire sensors
Selectable factory calibrated ranges up to 120A for increased exibility and
resolution
Factor y calibr ated switc h-se lec ta ble ranges (30/60/120A) for high resolution and
installation ease
No jumpers on unit...reduce installation error
Removable mounting bracket for installation exibility
Bracket can be installed in three dierent congurations...added exibility
Command relay switches up to 5A@250VAC
5-year warranty
SENSED AMPS
30/60/120A*
4mA
0A
20mA
SENSOR OUTPUT
*Factory calibrated ranges selected
with the amperage range switch
Load Trending And Control
Relay In One Package
Maximize Reliability
Minimize Installed Cost
SPECIFICATIONS
Sensor Power 30mA (max.)@12-30VDC
Insulation Class 600VAC RMS
Frequency Range 50/60 Hz
Temperature Range -15° to 60°C (5° to 140°F)
Humidity Range 10-90% RH non-condensing
Accuracy ±2% F.S. from 10% to 100% (selected range)
Response Time 2 sec.
Terminal Block Wire Size 24-14 AWG (0.2 to 2.1 mm
2
)
Terminal Block Torque 3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)
Agency Approvals UL 508 open device listing
Do not use LED status indicators as evidence of applied voltage
Current Sensors with Relay:
4-20mA Analog Output
Year
Warranty
5
H931
EXAMPLE LINEAR OUTPUT
Scale software as shown
H931 & H951
TM
HQ0001766.C 08131
Vue de la page 0
1 2

Résumé du contenu

Page 1 - 4-20mA Analog Output

current monitoringVERIS INDUSTRIES800.354.8556+1 503.598.4564www.veris.comDESCRIPTION The Hawkeye 931 and 951 provide accurate load trending informati

Page 2 - RELAY CONTACT RATINGS (N.O.)

current monitoring800.354.8556+1 503.598.4564www.veris.comMODEL AMPERAGE RANGE SENSOR OUTPUTRELAY TYPERELAY COIL RELAY RELAY POWER LED ULH9310 - 30/60

Commentaires sur ces manuels

Pas de commentaire