TM
CURRENT MONITORING
INSTALLATION GUIDE
Z201760-0E PAGE 1 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / suppor[email protected] 01121
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Split-Core Current Switch, Adjustable Trip Point
Installer’s Specifications
Amperage Range 1.25-50 A Continuous
External Supply Voltage 5-30 VDC
Insulation Class 600 VAC RMS (UL) 300 VAC RMS (CE)
Frequency 50/60 Hz
Temperature Range -15° to 6C (5° to 140°F)
Humidity Range 10-90% RH non-condensing
Hysteresis 10% typical
Status Output Ratings N.C. 0.1 A@5-30 VDC polarity sensitive
O State Resistance (max.) 34 µA@5 VDC; 200 µA@30 VDC
On State Voltage Drop 1.9 VDC (max.)@0.1 A
Terminal Block Max. Wire Size 14 AWG
Terminal Block Torque (nom.) 4 in-lbs (0.45 N-m)
Agency Approvals UL508, E150462
Specication Note: For CE compliance, conductor shall be insulated according to IEC 610101:2010,
Installation Category III or equivalent.
The unit design provides for basic insulation only.
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Follow safe electrical work practices.
See NFPA 70E in the USA, or applicable local codes.
This equipment must only be installed and serviced by qualified electrical personnel.
Read, understand and follow the instructions before installing this product.
Turn off all power supplying equipment before working on or inside the equipment.
Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
DANGER
WIRING EXAMPLE
H606
TM
606
DIMENSIONS
NOTICE
This product is not intended for life or safety applications.
Do not install this product in hazardous or classified locations.
The installer is responsible for conformance to all applicable codes.
Mount this product inside a suitable fire and electrical enclosure.
INSTALLATION
Disconnect and lock out power to the enclosure containing the
conductor to be monitored.
1. Locate a mounting surface for the removable mounting bracket that will allow
the monitored conductor to pass through the center window when it is installed
and that will keep the product at least 1/2” from any uninsulated conductors.
Determine cable routing for the controller connection, allowing wiring to reach
the mounting location.
2. Drill holes to mount the bracket to the chosen surface using the included screws.
3. Wire the output connections between the sensor and the controller (solid-state
contact) or external power supply.
4. Snap the sensor over the wire to be monitored and clip the assembly to the
mounting bracket.
5. Calibrate the sensor (see page 2) with the load running normally.
6. Secure enclosure and reconnect power.
Motor
Fan or Pump
DDC CONTROLLER
Insulated Conductor ONLY
DI
-
+
CONTACTOR
-
5-30VDC
POWER SOURCE
+
-
+
2.5" *
(64 mm)
2.1"
(54 mm)
3.5"
(89 mm)
2.9"
(74 mm)
0.4” x 0.2”
(10 mm x 5 mm)
Slot (2x)
1.2"
(31 mm)
Removable Mounting Bracket
0.7"
(18 mm)
0.5"
(13 mm)
2.1"
(54 mm)
1.0" *
(26 mm)
0.6"
(16 mm)
Vue de la page 0
1 2

Résumé du contenu

Page 1 - INSTALLATION GUIDE

TMCURRENT MONITORINGINSTALLATION GUIDEZ201760-0E PAGE 1 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 01121Alt

Page 2 - CAUTION

Z201760-0E PAGE 2 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 01121Alta Labs, Enercept, Enspector, Hawkeye,

Commentaires sur ces manuels

Pas de commentaire