current monitoring
VERIS INDUSTRIES
800.354.8556
+1 503.598.4564
www.veris.com
DESCRIPTION
The Hawkeye 40 Series combines a switching relay, a current status sensor, and a
Hand-O-Auto (HOA) switch into a single nipple-mounted housing. The low voltage
and line voltage wires are functionally separated from each other. A hinged lid on the
low voltage side allows easy relay connection and trip point adjustment, while the
high voltage side is closed for added safety. The H40 is connected in series between
the power source and the motor, and the relay and HOA switch control the on/o
functioning of the motor.
APPLICATIONS
Monitoring status and controlling small motor loads that are not driven by a
motor starter or contactor
• Exhaust fans
• Unit ventilators
• Fan terminal units
• Fan coil units
• Recirculating pumps
FEATURES
Separate high and low voltage sections...fast and economical installation by
low voltage electricians
Combines status sensor, command relay, and HOA switch in a single series
circuit...one line connection for three devices
Remote mounted enclosure eliminates the need to cram multiple devices into a
junction box
HOA provides true relay control...ideal for troubleshooting control wiring
SPST relay is eld-selectable for N.O. or N.C. operation (some models)
5-year warranty
Line and Low Voltage
Separated Fractional Motor
Status with Command Relay
Field Mount Motor
Control Device
SPECIFICATIONS
Sensor Power (H40NE8A and H40ME8X only) Induced
Operating Temperature Range -15°C to 50°C (5° to 122°F)
Operating Humidity Range 0-95% RH non-condensing
Frequency Range 50-60 Hz
Wire to Relay Contacts H40 NE8A, H40NEXA, H40ME8X, H40MEXX: use 12 AWG (3.3 mm
2
) or larger wire
H40BAXA, H40AAXX: use 16 AWG (1.3 mm
2
) or larger wire
Low Voltage Terminal Block Wire Size 24-14 AWG (0.2 to 2.1 mm
2
)
Low Voltage Terminal Block Torque 3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)
Relay:
Relay Contact Ratings H40NE8A, H40NEXA: 16A@120/250VAC, 12A@277VAC, 1HP@120VAC, 8A@28VDC
H40ME8X, H40MEXX: SPDT 16A@120/277VAC, 1HP@120VAC, 2HP@277VAC, 16A@28VDC
H40BAXA: 10A@120/240/277VAC, 1/3HP@120VAC, 8A@28VDC
H40AAXX: SPDT 10A@120/240/277VAC, 1/3HP@120VAC, 10A@28VDC
Relay Coil Ratings H40NE8A, H40ME8X, H40MEXX, H40NEXA: 24VDC 45mA nom.; 24VAC 78mA nom.; Class 2*
H40AAXX, H40BAXA: 10-30VAC@24-38mA; 10-30VDC@10-16mA; Class 2*
Agency Approvals UL 508 open device listing
* In addition, coil input from other sources may be used as detailed in NEC 2008, Article 725.121.
Year
Warranty
5
H40
H40 SERIES
TM
HQ0001770.B 01131
Vue de la page 0
1 2

Résumé du contenu

Page 1 - Control Device

current monitoringVERIS INDUSTRIES800.354.8556+1 503.598.4564www.veris.comDESCRIPTIONThe Hawkeye 40 Series combines a switching relay, a current statu

Page 2 - APPLICATION/WIRING DIAGRAM

current monitoring800.354.8556+1 503.598.4564www.veris.comORDERING INFORMATIONDIMENSIONAL DRAWINGMOUNTING OPTIONSAPPLICATION/WIRING DIAGRAMMODEL AMPER

Commentaires sur ces manuels

Pas de commentaire