CURRENT MONITORING
INSTALLATION GUIDE
Z202138-0A PAGE 1 ©2008 Veris Industries USA 800.354.8556 or 503.598.4564 / support@veris.com 09082
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Solid-Core Current Transducer,
0-5VDC Output
Installer’s Specifications
Sensor Power Induced from monitored conductor
Insulation Class 600VAC RMS
Amperage Range 0-10A
Frequency 50/60Hz nominal
Temperature Range -15° to 60°C (5° to 140°F)
Humidity Range 10-90% RH, non-condensing
Accuracy ±2% F.S. from 10% to 100%
Response Time 2 sec.
Terminal Block Maximum Wire Size 14 AWG
Terminal Block Torque (nominal) 4 in-lbs (0.45 N-m)
For applications requiring double or reinforced insulation, please contact the factory.
)";"3%0'&-&$53*$4)0$,&91-04*0/03"3$'-"4)
t 'PMMPXTBGFFMFDUSJDBMXPSLQSBDUJDFT
4FF/'1"&JOUIF64"PSBQQMJDBCMFMPDBMDPEFT
t 5IJTFRVJQNFOUNVTUPOMZCFJOTUBMMFEBOETFSWJDFECZRVBMJmFEFMFDUSJDBMQFSTPOOFM
t 3FBEVOEFSTUBOEBOEGPMMPXUIFJOTUSVDUJPOTCFGPSFJOTUBMMJOHUIJTQSPEVDU
t 5VSOPõBMMQPXFSTVQQMZJOHFRVJQNFOUCFGPSFXPSLJOHPOPSJOTJEFUIFFRVJQNFOU
t 6TFBQSPQFSMZSBUFEWPMUBHFTFOTJOHEFWJDFUPDPOmSNQPXFSJTPõ
%0/05%&1&/%0/5)*4130%6$5'0370-5"(&*/%*$"5*0/
t 0OMZJOTUBMMUIJTQSPEVDUPOJOTVMBUFEDPOEVDUPST
'BJMVSFUPGPMMPXUIFTFJOTUSVDUJPOTXJMMSFTVMUJOEFBUIPSTFSJPVTJOKVSZ
%"/(&3
Wiring ExamplE
H822 822
DimEnsions
/05*$&
t 5IJTQSPEVDUJTOPUJOUFOEFEGPSMJGFPSTBGFUZBQQMJDBUJPOT
t %POPUJOTUBMMUIJTQSPEVDUJOIB[BSEPVTPSDMBTTJmFEMPDBUJPOT
t 5IFJOTUBMMFSJTSFTQPOTJCMFGPSDPOGPSNBODFUPBMMBQQMJDBCMFDPEFT
t .PVOUUIJTQSPEVDUJOTJEFBTVJUBCMFmSFBOEFMFDUSJDBMFODMPTVSF
quick install
Disconnect and lock out power.1.
Install the mounting bracket to the back of the electrical enclosure, no closer than 2.
½” (12mm) to an uninsulated conductor.
Slide the conductor to be monitored through the sensing hole of the current 3.
switch. Terminate the conductor. See Notes (page 2) for currents under 1 Amp or
above 10 Amp.
Wire the output connections between the H822 and the controller (0-5VDC).4.
Reconnect power.5.
Scale the controller software to match the H822s output.6.
ø 0.7"
(18 mm)
0.4” x 0.2”
Slot (x2)
2.8"
(71 mm)
1.7
(43 mm)
2.3"
(58 mm)
1.1"
(27 mm)
0.9"
(23 mm)
Removable/Adjustable Mounting Bracket
Fan or Pump
CONTROLLER
0-5VDC
COMM
+
AI
Insulated Conductor Only
CONTACTOR