PAGE 1 ©2010 Veris Industries USA 800.354.8556 or 1.503.598.4564 / suppor[email protected] 06101Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Wall Mount with Analog Setpoints, LCD Display,
1% NIST, 2% NIST, 2%, 3%, or 5%
Installer’s Specifications
Power Supply* 15 to 24VDC/24VAC, 100mA max.
Outputs, Analog Switch Selectable 4-20mA or 0-10V/0-5VDC (switch affects both outputs)
RH Sensor Digitally profiled thin-film capacitive (32-bit mathematics)
U.S. Patent 5,844,138
Accuracy at 25°C from 10-80% RH** ±2%, 3%, or 5% models
±1% at 20-50% RH (Multi-point calibration NIST traceable)
Reset Rate*** 24 hours
Stability ±1% @ 20°C (68°F) annually, for two years
Linearity Included in Accuracy spec.
Operating Humidity Range 0-100% RH
Temperature Coefficient ±0.1%RH/°C above or below 25°C (typical)
Operating Temperature Range 10° to 35°C (50° to 95°F)
Scaling 0-100% RH
Calibration Offset Adjustable ±9.9% in 0.1% increments
Setpoint Range 10-80% RH in 1% increments
*One side of transformer secondary is connected to signal common, so an isolation transformer or
dedicated power supply may be required.
**Specified accuracy with 24VDC supplied power with rising humidity.
***Reset Rate is time required to recover to 50% RH after exposure to 90% RH for 24 hours.
To maintain CE compliance the connected power supply must have a CE mark supporting LV + CE
directives.
HWS SerieS HWS SerieS
Dimensions
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• Read and understand the instructions before installing
this product.
• Turn off all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
ProDuct iDentification
quick install
Select a mounting location away from ventilation sources. The sensor should be 1.
mounted on a vertical wall, about 4 ½ feet above the floor.
Affix the backplate to the wall.2.
Wire the device. Refer to wiring diagram.3.
Install Cover. 4.
1.2"
(29 mm)
3.5"
(89 mm)
4.75"
(121 mm)
-+
Enter
SetpointAccuracy NIST
= Analog
1 = 1%
2 = 2%
3 = 3%
5 = 5%
HWS
RH Only Device
N = NIST (1 & 2% only)
X = No (2, 3, 5% only)