Installation Guide
Power Monitoring
ZL0108-0D Page 1 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / suppor[email protected] 10131
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
TM
For use in a Pollution Degree 2 or better environment only. A Pollution Degree 2
environment must control conductive pollution and the possibility of condensation or
high humidity. Consider the enclosure, the correct use of ventilation, thermal properties
of the equipment, and the relationship with the environment. Installation category:
CAT II or CAT III. Provide a disconnect device to disconnect the meter from the supply
source. Place this device in close proximity to the equipment and within easy reach of
the operator, and mark it as the disconnecting device. The disconnecting device shall
meet the relevant requirements of IEC 60947-1 and IEC 60947-3 and shall be suitable for
the application. In the US and Canada, disconnecting fuse holders can be used. Provide
overcurrent protection and disconecting device for supply conductors with approved
current limiting devices suitable for protecting the wiring. If the equipment is used in a
manner not specied by the manufacturer, the protection provided by the device may
be impaired.
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
This equipment must only be installed and serviced by qualified electrical personnel.
Read, understand and follow the instructions before installing this product.
Turn off all power supplying equipment before working on or inside the equipment.
Any covers that may be displaced during the installation must be reinstalled
before powering the unit.
Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
Failure to follow these instructions will result in death or serious injury.
A qualied person is one who has skills and knowledge related to the construction and
operation of this electrical equipment and the installation, and has received safety
training to recognize and avoid the hazards involved. NEC2009 Article 100
No responsibility is assumed by Veris Industries for any consequences arising out of the
use of this material.
DANGER
NOTICE
This product is not intended for life or safety applications.
Do not install this product in hazardous or classified locations.
The installer is responsible for conformance to all applicable codes.
Mount this product inside a suitable fire and electrical enclosure.
FCC PART 15 INFORMATION
NOTE: This equipment has been tested by the manufacturer and found to
comply with the limits for a class B digital device, pursuant to part 15 of
the FCC Rules. These limits are designed to provide reasonable protection
against harmful interference when the equipment is operated in a
residential environment. This equipment generates, uses, and can radiate
radio frequency energy and, if not installed and used in accordance with
the instruction manual, may cause harmful interference to radio
communications. This device complies with part 15 of the FCC Rules.
Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and
(2) this device must accept any interference received, including
interference that may cause undesired operation.
Modifications to this product without the express authorization of the
manufacturer nullify this statement.
WARNING
LOSS OF CONTROL
Assure that the system will reach a safe state during and after a control path failure.
∙ Separate or redundant control paths must be provided for critical control functions.
∙ Test the eect of transmission delays or failures of communication links.
1
∙ Each implementation of equipment using communication links must be individually
and thoroughly tested for proper operation before placing it in service.
Failure to follow these instructions may cause injury, death or equipment damage.
1
For additional information about anticipated transmission delays or failures of the link, refer to
NEMA ICS 1.1 (latest edition). Safety Guidelins for the Application, Installation, and Maintenance
of Solid-State Control or its equivalent in your specic country, language, and/or location.
Control system design must consider the potential failure modes of control paths and, for
certain critical control functions, provide a means to acheive a safe state during and after a
path failure. Examples of critical control functions are emergency stop and over-travel stop.
Product Identification
Model Description
E50F2 LON output, 1 pulse input , alarm output
E50F5 LON output, data logging, 2 pulse inputs
Product Overview
The E50Fx DIN Rail Power Meter provides a solution for measuring energy data with a single device. Inputs include
pulse, control power, CT, and 3-phase voltage. The E50Fx supports multiple output options, including solid state
phase loss alarm relay contacts (E50F2 only), LON, and data logging (E50F5 only). The LCD screen on the faceplate
allows instant output viewing.
The meter is housed in a plastic enclosure suitable for installation on T35 DIN rail according to EN50022. The E50 can
be mounted with any orientation over the entire ambient temperature range, either on a DIN rail or in a panel. The
meter is not sensitive to CT orientation to reduce installation errors.
E50F2, E50F5
Compact Power and Energy Meters
With LON TP/FT-10 Communication
Specifications
MEASUREMENT ACCURACY
Real Power and Energy
IEC 62053-22 Class 0.5S, ANSI C12.20 0.5%
Reactive Power and Energy
IEC 62053-23 Class 2, 2%
Current
0.4% (+0.015% per °C deviation from 2C) from 5% to 100% of range;
0.8% (+0.015% per °C deviation from 2C) from 1% to 5% of range
Voltage
0.4% (+0.015% per °C deviation from 2C) from 90 V
L- N
to 600 VAC
L- L
Sample Rate
2520 samples per second
Data Update Rate
1 sec
Type of Measurement
True RMS up to 1260 Hz (21st harmonic at 60 Hz); One to three phase AC
system
INPUT VOLTAGE CHARACTERISTICS
Measured AC Voltage
Minimum 90 V
L- N
(156 V
L- L
) for stated accuracy;
UL Maximums: 600 V
L- L
(347 V
L- N
); CE Maximum: 300 V
L- N
Metering Over-Range
+20%
Impedance
2.5 MΩ
L- N
/5 MΩ
L- L
Frequency Range
45 to 65 Hz
INPUT CURRENT CHARACTERISTICS
CT Scaling
Primary: Adjustable from 5 A to 32,000 A
Measurement Input Range
0 to 0.333 VAC or 0 to 1.0 VAC (+20% over-range), rated for use with Class
1 voltage inputs
Impedance
10.6 kΩ (1/3 V mode) or 32.1 kΩ (1 V mode)
RoHS
Compliant
Vue de la page 0
1 2 3 4 5 6 ... 33 34

Résumé du contenu

Page 1 - E50F2, E50F5

Installation GuidePower MonitoringZL0108-0D Page 1 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 10131 Alt

Page 2 - Specifications

ZL0108-0D Page 10 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 10131 Alta Labs, Enercept, Enspector, Hawk

Page 3 - Table of Contents

ZL0108-0D Page 11 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 10131 Alta Labs, Enercept, Enspector, Hawk

Page 4 - Data Outputs

ZL0108-0D Page 12 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 10131 Alta Labs, Enercept, Enspector, Hawk

Page 5 - 

ZL0108-0D Page 13 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 10131 Alta Labs, Enercept, Enspector, Hawk

Page 6 - Installation

ZL0108-0D Page 14 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 10131 Alta Labs, Enercept, Enspector, Hawk

Page 7 - Wiring Symbols

ZL0108-0D Page 15 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 10131 Alta Labs, Enercept, Enspector, Hawk

Page 8

ZL0108-0D Page 16 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 10131 Alta Labs, Enercept, Enspector, Hawk

Page 9 - Control Power

ZL0108-0D Page 17 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 10131 Alta Labs, Enercept, Enspector, Hawk

Page 10 - Pulse Contact Inputs

ZL0108-0D Page 18 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 10131 Alta Labs, Enercept, Enspector, Hawk

Page 11 - Communications

ZL0108-0D Page 19 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 10131 Alta Labs, Enercept, Enspector, Hawk

Page 12 - Menu Abbreviations

ZL0108-0D Page 2 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 10131 Alta Labs, Enercept, Enspector, Hawke

Page 13 - EF, EF

ZL0108-0D Page 20 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 10131 Alta Labs, Enercept, Enspector, Hawk

Page 14

ZL0108-0D Page 21 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 10131 Alta Labs, Enercept, Enspector, Hawk

Page 15

ZL0108-0D Page 22 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 10131 Alta Labs, Enercept, Enspector, Hawk

Page 16

ZL0108-0D Page 23 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 10131 Alta Labs, Enercept, Enspector, Hawk

Page 17 - Using the LNS

ZL0108-0D Page 24 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 10131 Alta Labs, Enercept, Enspector, Hawk

Page 18 - Plugin (cont.)

ZL0108-0D Page 25 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 10131 Alta Labs, Enercept, Enspector, Hawk

Page 19

ZL0108-0D Page 26 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 10131 Alta Labs, Enercept, Enspector, Hawk

Page 20

ZL0108-0D Page 27 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 10131 Alta Labs, Enercept, Enspector, Hawk

Page 21

ZL0108-0D Page 28 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 10131 Alta Labs, Enercept, Enspector, Hawk

Page 22

ZL0108-0D Page 29 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 10131 Alta Labs, Enercept, Enspector, Hawk

Page 23

ZL0108-0D Page 3 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 10131 Alta Labs, Enercept, Enspector, Hawke

Page 24 - Without the Plugin

ZL0108-0D Page 30 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 10131 Alta Labs, Enercept, Enspector, Hawk

Page 25 - Network Variables

ZL0108-0D Page 31 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 10131 Alta Labs, Enercept, Enspector, Hawk

Page 26 - Network Variables (cont.)

ZL0108-0D Page 32 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 10131 Alta Labs, Enercept, Enspector, Hawk

Page 27

ZL0108-0D Page 33 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 10131 Alta Labs, Enercept, Enspector, Hawk

Page 28

ZL0108-0D Page 34 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 10131 Alta Labs, Enercept, Enspector, Hawk

Page 29

ZL0108-0D Page 4 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 10131 Alta Labs, Enercept, Enspector, Hawke

Page 30 - Configuration Properties

ZL0108-0D Page 5 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 10131 Alta Labs, Enercept, Enspector, Hawke

Page 31

ZL0108-0D Page 6 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 10131 Alta Labs, Enercept, Enspector, Hawke

Page 32

ZL0108-0D Page 7 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 10131 Alta Labs, Enercept, Enspector, Hawke

Page 33

ZL0108-0D Page 8 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 10131 Alta Labs, Enercept, Enspector, Hawke

Page 34 - (EFUPTable)

ZL0108-0D Page 9 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 10131 Alta Labs, Enercept, Enspector, Hawke