Veris-industries H681x-V SERIES Datasheet Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Équipement Veris-industries H681x-V SERIES Datasheet. Veris Industries H681x-V SERIES Datasheet User Manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 2
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
POWER Metering CTS
VERIS INDUSTRIES
800.354.8556
+1 503.598.4564
www.veris.com
Medium Current Ranges
DESCRIPTION
The E682x and H681x-V Series of current transducers provide a safe voltage output
for use with data loggers, chart recorders, and power monitoring equipment. E682x
devices are solid-core with 0-0.333VAC output, while H681x CTs are split-core and
have 0-0.333VAC and 1VAC output options.
APPLICATIONS
Data logging
Recording
Power monitoring
Energy management
Alternative energy monitoring
Cost allocation
Current Transducers,
Voltage Output
SPECIFICATIONS (Solid-Core)
Inputs:
Frequency Range 50/60 Hz
Leads 6’ (1.8 m)
Accuracy:
Accuracy ±0.5% of reading from 5% to 120% of rated current
Outputs:
Output at Rated Current 0.333VAC
Mechanical:
Insulation 600VAC
Environmental:
Operating Temperature Range -40° to 85°C (40° to 185°F)
Storage Temperature Range -50° to 105°C (-58° to 221°F)
Humidity Range 0-95% noncondensing
Installation Category Cat III, pollution degree 2
Agency Approvals UL61010-1, EN61010-1
SPECIFICATIONS (Split-Core)
Inputs:
Frequency Range 50/60 Hz
Leads 6 ft (1.8 m)
Accuracy:
Accuracy ±1% of reading from 10% to 100% of rated current
Outputs:
Output at Rated Current 0.333 or 1VAC
Mechanical:
Insulation 600VAC
Environmental:
Operating Temperature Range 2400A models only: -15° to 50°C (5° to 122°F); All other models: -15° to 60°C (5° to 140°F)
Storage Temperature Range -40° to 70°C (-40° to 158°F)
Humidity Range 0-95% noncondensing
Agency Approvals UL61010, EN61010
H681x-V
Ex & Hx-VSERIES
FEATURES
High accuracy: ±0.5% from 5% to 120% of rated current for E682x or ±1%
from 10% to 100% of rated current for H681x
0.333V and 1VAC output versions available
UL recognized
E682x
HQ0001818.D 01131